3401.17.A

Produktnummer: 22543736
Huber Suhner
Lagerbeholdning:

H+S
Side of bulkhead protected side
Gas tube Yes DC, GDT not included
Moisture resistance according MIL-STD-202, Method 106
Impedance 50 Ω
Vibration according MIL-STD-202, Method 204, Cond. D
Storage temperature -40 °C ... 85 °C
Operation temperature -40 °C ... 85 °C
Residual pulse energy (typ.) 350 µJ (test pulse 4 kV 1.2/50 µs; 2 kA 8/20 µs)
Product description GDT technology up to 1.0 GHz
Thermal shock according MIL-STD-202, Method 107, Cond. B
Insertion loss typical ≤ 0.1 dB
Product code 3401.17.A
Main path connectors Port 1: unprotected, N jack (female)Port 2: protected, N jack (female)
Housing material / plating Brass / SUCOPLATE (R) Plating
Electrical remarks Data refer to GDT 9071.99.0547, 230 V
Ingress protection (IP Rating) IP66
Frequency frame 0 MHz to 1000 MHz
Mounting and grounding MH12 (bulkhead mounting)
Residual pulse voltage (typ.) 650 V (test pulse 4 kV 1.2/50 µs; 2 kA 8/20 µs)
Return loss typical ≥ 26.44 dB
Surge current handling capability 30 kA single, 20 kA multiple (test pulse 8/20 µs)
Center contact, material / plating Port 1: Copper Beryllium Alloy / Gold Plating (without Nickel underplating)Port 2: Copper Beryllium Alloy / Gold Plating (without Nickel underplating)
EMP can be install reversed YES
Mating cycles 500
CW power frame ≤ 150 W
Weight 110 g